This fault indicates that an external device triggered a fault via the Multi-Function Digital Input (MFDI) terminal S3, or there is incorrect wiring to S3, or the terminal is incorrectly configured for an external fault despite not being in use. This causes the drive to halt operation based on an external signal, potentially stopping connected machinery.
Click steps to track your progress.
Inspect all wiring connections to terminal S3, ensuring they are tight and properly terminated.
Verify the operational status of the external device connected to S3. Check its local indicator or output state.
Review the drive parameter (e.g., P2-03) assigned to S3 and confirm it is configured for the correct function (e.g., External Fault 3, Emergency Stop).
Use a multimeter to measure the voltage present at terminal S3 relative to SC (common) to confirm the signal state.
Isolate the external device by disconnecting it from S3 and checking if the fault persists. If it clears, troubleshoot the device itself.