Err

EEPROM Write Error

Yaskawa · V1000

What does Err mean?

This fault signals a hardware problem with the drive's EEPROM or data corruption during a write operation, often due to electrical interference. The drive may not be able to reliably store or retrieve critical parameters, leading to unpredictable behavior or loss of configuration. Continuous operation risks data integrity and proper control.

Common Causes

  • Electrical noise or power fluctuations (voltage dips or spikes) during a parameter write operation to the EEPROM.
  • Failure of the EEPROM memory chip itself, preventing data from being reliably written or stored.
  • Attempting to write an invalid parameter value or a parameter out of its allowed range, causing a write protection error.
  • Firmware bug causing an internal error during the EEPROM write routine, possibly due to a corrupted firmware image.
  • Exceeding the maximum number of write cycles for the EEPROM, leading to wear-out over long periods of frequent parameter changes.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Reset power to the drive and attempt the parameter write operation again.

  2. 2

    Verify the stability of the control power supply (e.g., 24VDC at control terminals) using a multimeter during write operations.

  3. 3

    Check the parameter values being written to ensure they are within the acceptable range for the drive model (consult manual).

  4. 4

    Perform an all-parameter initialization (e.g., P1-03 = 2220) to clear any potentially corrupted memory sectors, then retry the write operation.

  5. 5

    If using a programming tool (e.g., DriveWorksEZ), ensure the software is updated and compatible with the drive's firmware version.

Browse all codes in this manual (87)
Verified technical data. Last updated: April 2026

Related Faults

Base BlockBase Block Function ActiveBraking Transistor FaultInternal Braking Transistor FaultCECommunication Error
Source: Yaskawa V1000
View Official PDFSearch more codes in this manual