Yaskawa · V1000
A parameter or function has been configured that is not supported or compatible with the currently selected control mode of the drive. This error often arises after a control mode change, requiring a thorough review of parameter settings to match the new mode of operation.
Click steps to track your progress.
1. Identify the currently selected drive control method by checking Parameter A1-02.
2. Determine which specific parameter or function (often indicated by the fault message or recent changes) is causing the incompatibility.
3. Refer to the drive's programming manual to verify which parameters and functions are compatible with the control mode set in A1-02.
4. Either change the incompatible parameter/function to a compatible setting or adjust Parameter A1-02 to a control mode that supports the desired function.
5. Perform a parameter initialization (Parameter A1-03) to reset all parameters to default for the current control mode, then reconfigure from scratch if necessary.
6. Perform a drive power cycle after setting the parameters.