OH3

Motor Overheat Alarm (Level 3)

Yaskawa · E7 Drive

What does OH3 mean?

This alarm indicates that the motor's temperature, as monitored by an analog input (H3-09=E), has exceeded the OH3 alarm threshold (1.17V). It serves as an early warning of potential motor overheating, allowing for intervention before a more critical fault occurs that could lead to a drive stop.

Common Causes

  • Motor operating under sustained heavy load, causing its internal temperature to rise above normal limits.
  • Inadequate motor cooling due to blocked motor fan, dirty motor fins, or high ambient temperature around the motor.
  • Motor winding insulation degradation leading to localized hot spots within the motor.
  • Incorrect scaling or wiring of the analog temperature sensor (e.g., PTC, NTC, RTD) connected to input H3-09.
  • High drive output current due to mis-tuned motor parameters (e.g., E1-01) or excessive motor slip.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Verify the analog input signal at terminal H3-09 is correctly wired and scaled, measuring the voltage during motor operation.

  2. 2

    2. Measure the motor surface temperature using an infrared thermometer and compare it to the motor's rated operating temperature.

  3. 3

    3. Inspect the motor's cooling fan for proper operation and ensure cooling fins are free of debris and obstructions.

  4. 4

    4. Reduce the mechanical load on the motor if it is consistently running at high current, causing thermal stress.

  5. 5

    5. Check for any phase current imbalance at the drive output (U, V, W terminals) that could indicate internal motor issues.

Browse all codes in this manual (64)
Verified technical data. Last updated: March 2026

Related Faults