OPE01

kVA Selection Error

Yaskawa · E7 Drive

What does OPE01 mean?

An Operator Programming Error occurs when the Drive's kVA setting is incorrect, usually after a control board replacement. The Drive will not operate until this parameter is corrected.

Common Causes

  • Control board replaced without correctly setting the kVA (or drive size) parameter for the specific power section, resulting in a mismatch.
  • Incorrect dip switch setting or internal jumper configuration on the control board for kVA selection, not matching the drive's physical rating.
  • Parameter (e.g., A1-02, or an internal diagnostic code) that defines the drive's kVA rating was manually misconfigured.
  • Firmware mismatch or corruption after a control board replacement leading to misinterpretation of kVA settings.
  • Control board incompatibility with the installed power section.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Consult the drive's hardware manual to locate the kVA selection method (e.g., dip switches, jumpers, or parameter A1-02) on the control board.

  2. 2

    2. Verify the physical kVA selection (switches/jumpers) on the control board matches the drive's nameplate kVA rating. Adjust as needed.

  3. 3

    3. If kVA is set via parameter (e.g., A1-02), ensure it is programmed to the correct value corresponding to the drive's power section rating.

  4. 4

    4. Power cycle the drive (turn off for 30 seconds, then on) after making any kVA selection corrections to allow the new setting to take effect.

  5. 5

    5. If issue persists, check the firmware version of the control board and ensure it is compatible with the power section of the drive.

Browse all codes in this manual (64)
Verified technical data. Last updated: March 2026

Related Faults