HISUC

High Suction Pressure

Yaskawa · iQpump1000

What does HISUC mean?

The suction pressure has risen above the level set in Q5-12 for longer than the time set in Q5-13. This fault is effective only when Q5-14 (High Suction Pressure Behavior Select) is set to 2 (fault).

Common Causes

  • System suction pressure is too high, exceeding the Q5-12 threshold for the Q5-13 duration.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Reduce the system pressure.

  2. 2

    Set the High Suction Pressure fault characteristics using parameters Q5-12, Q5-13, and Q5-18.

  3. 3

    Control drive response to this condition using Q5-14 (High Suction Pressure Behavior Select).

  4. 4

    Control auto-restart of this fault using Q5-14 (High Suction Pressure Behavior Select) and Q5-15 (Suction Pressure Auto-restart Time).

Browse all codes in this manual (45)
Verified technical data. Last updated: March 2026

Related Faults