LOSUC

Low Suction Pressure

Yaskawa · iQpump1000

What does LOSUC mean?

The suction pressure has fallen below the level set in Q5-09 for longer than the time set in Q5-10. This fault is effective only when Q5-11 (Low Suction Pressure Behavior Select) is set to 2 (fault).

Common Causes

  • System suction pressure has fallen below the configured threshold.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Increase the system pressure.

  2. 2

    Set the Low Suction fault characteristics using parameters Q5-09, Q5-10, and Q5-18.

  3. 3

    Control drive response to this condition using Q5-11 (Low Suction Pressure Behavior Select).

  4. 4

    Control auto-restart of this fault using Q5-11 (Low Suction Pressure Behavior Select) and Q5-15 (Suction Pressure Auto-restart Time).

Browse all codes in this manual (45)
Verified technical data. Last updated: March 2026

Related Faults