MSL

Net Master Lost

Yaskawa · iQpump1000

What does MSL mean?

The MEMOBUS master has been lost, meaning no message has been received from the master within the time set in P9-26. This fault occurs when P9-27 (Network Recovery) is set to 3 (Fault MSL).

Common Causes

  • No message received from the master within the time set in P9-26.
  • Network Recovery (P9-27) is set to 3 (Fault MSL).
  • Faulty network connections.
  • Incorrect H5-01 or P9-25 settings on network drives.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Increase the P9-26 setting to account for network latency.

  2. 2

    Verify that a drive on the network has parameter P1-01 set to 3 and P9-27 set to 0 to act as a master.

  3. 3

    Check network connections for integrity.

  4. 4

    Verify H5-01 and P9-25 settings for all drives on the network are correct.

Browse all codes in this manual (45)
Verified technical data. Last updated: March 2026

Related Faults