Traduciendo...
C003

Error Muting Lamp

ABB · AC500-S Safety Controller

¿Qué significa C003 ?

An error has been detected concerning the muting lamp for an AOPD (Active Opto-electronic Protective Device). A faulty muting lamp (indicated by S_MutingLamp = FALSE) prevents the proper visual signaling of the muting state, which is crucial for operator safety. This can lead to an unsafe condition if the lamp fails to indicate muting correctly, potentially allowing access to a hazardous area during muting.

Causas comunes

  • Failure of the muting lamp itself (e.g., 24VDC LED stack light) due to burnout or internal open circuit.
  • Open circuit in the wiring connecting the muting lamp to its control output (e.g., OSSD output from the muting module or PLC output).
  • Failure of the digital output channel (e.g., safety relay output, PLC output Q0.1) responsible for powering the muting lamp.
  • Incorrect electrical specifications of the muting lamp (e.g., current draw too high) causing premature failure or detection issues by the muting module.
  • Internal fault within the AOPD muting module (e.g., Sick Flexi Classic, Rockwell GuardShield) preventing correct current sensing or feedback loop operation for the lamp.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the voltage at the muting lamp terminals (e.g., X3.1 and X3.2) using a multimeter when the lamp is commanded ON; expect supply voltage (e.g., 24VDC).

  2. 2

    Perform a continuity test on the muting lamp's internal elements (e.g., filament, LED array) with an ohmmeter, after disconnecting it from power; an open circuit indicates lamp failure.

  3. 3

    Inspect the wiring from the muting module's lamp output (e.g., Y1/Y2) to the lamp for breaks, loose connections, or corrosion; test continuity of each wire segment.

  4. 4

    Check the status of the digital output (e.g., PLC output module Q0.1 or safety relay output) controlling the muting lamp using PLC diagnostics or by measuring voltage at the output terminal.

  5. 5

    Temporarily replace the muting lamp with a known-good lamp of the same voltage and wattage specification to confirm if the lamp unit is faulty.

  6. 6

    Consult the AOPD muting module's diagnostic indicators (e.g., onboard LEDs, fault codes on an HMI) to identify specific internal module errors related to lamp supervision.

Ver todos los códigos en este manual (48)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: ABB AC500-S Safety Controller