Transmission error: timeout (F_WD_Time or F_WD_Time_2 elapsed)
ABB · AC500
¿Qué significa 25 ?
A transmission error due to a timeout occurred in PROFIsafe communication, meaning that the expected response was not received within the specified F_WD_Time or F_WD_Time_2 watchdog period. This can lead to a safety function interruption if communication is critical.
Causas comunes
- Interruption or disconnection of the PROFIBUS/PROFINET cable between the safety PLC and the I/O module.
- Incorrect termination resistors at the end of a PROFIBUS segment or incorrect cable categories for PROFINET.
- The PROFIsafe watchdog time parameter (e.g., F_WD_Time) is set too short for the actual network load or latency.
- Severe electromagnetic interference (EMI) corrupting PROFIsafe telegrams, causing retransmissions and timeouts.
- Faulty PROFIBUS/PROFINET communication interface on either the safety PLC or the safety I/O module.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
1. Check the physical integrity and secure connection of the PROFIBUS/PROFINET cable at both ends of the segment.
- 2
2. Verify that the bus termination resistors are correctly installed and switched 'ON' at the bus segment's start and end points.
- 3
3. Using a network diagnostic tool, check the PROFIBUS/PROFINET network for telegram errors, retransmissions, or missing frames.
- 4
4. Review and potentially increase the F_WD_Time or F_WD_Time_2 watchdog parameters in the safety configuration.
- 5
5. Isolate the suspected faulty module (safety PLC or safety I/O) by temporarily swapping it with a known good unit (if available).