Traduciendo...
263

Measurement Underflow

ABB · AC500

¿Qué significa 263 ?

This error indicates that the measured signal value on an analog input channel is below the minimum range or threshold the I/O module expects. Possible causes include a disconnected sensor, a sensor providing too low a signal, or a problem with the sensor's power supply, resulting in no meaningful input.

Causas comunes

  • The analog sensor is disconnected, or an open circuit exists in the wiring between the sensor and the I/O module.
  • The sensor itself has failed and is not outputting any signal or is stuck at its minimum output value (e.g., 0mA, 0V).
  • Incorrect scaling parameter (e.g., P3-00 'Min Analog Input Value') configured in the I/O module's settings.
  • Loss of power supply to the analog sensor, preventing it from generating an output signal.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Verify that the analog sensor's power supply (e.g., 24VDC) is present and within specified limits.

  2. 2

    2. Measure the actual analog signal (e.g., current or voltage) at the sensor's output terminals.

  3. 3

    3. Using a multimeter, check the continuity of the wiring from the sensor to the analog input terminals on the I/O module.

  4. 4

    4. Verify that the configured input range parameter (e.g., P3-00 or scaling limits) in the I/O module matches the sensor's output range.

  5. 5

    5. Temporarily connect a known good signal source (e.g., 4-20mA generator) to the analog input to test the module.

Ver todos los códigos en este manual (54)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas