FF80

DC High Rush

ABB · ACS560 Standard Control Program Firmware

¿Qué significa FF80 ?

The drive's supply voltage is excessive, exceeding 124% of the unit's voltage rating. When this occurs, the motor speed can rapidly accelerate (rush) to a trip level (40% of nominal speed), indicating a potentially damaging overvoltage condition for the drive and potentially the motor.

Causas comunes

  • Input supply voltage transients or spikes exceeding the drive's maximum input voltage rating (e.g., 400V drive seeing >500V momentarily).
  • Incorrect drive nominal voltage parameter (e.g., P02-01) configured lower than the actual supply voltage.
  • Failure of input voltage sensing circuit within the drive, leading to misinterpretation of supply voltage.
  • Severe line voltage imbalance or phase loss causing instability in the DC bus charging.
  • Faulty power module components allowing uncontrolled DC bus voltage rise.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the actual input AC supply voltage at the drive's L1/L2/L3 terminals using a true RMS voltmeter or power analyzer.

  2. 2

    Verify the drive's nominal voltage parameter (e.g., P02-01) is correctly set to match the actual supply voltage.

  3. 3

    Monitor the DC bus voltage (e.g., r0026) during power-up and operation to identify rapid voltage increases.

  4. 4

    Inspect the input power wiring for loose connections or corroded terminals that could cause transient voltage spikes.

  5. 5

    Check for the presence of severe voltage sags or swells on the supply line that could trigger an overvoltage condition when recovering.

Ver todos los códigos en este manual (33)