Traduciendo...
A591

Drive HW initialization

ABB · ACS580

¿Qué significa A591 ?

The drive's hardware is undergoing its initialization process. While typically a brief startup event, persistent initialization can signal a deeper issue with the drive's hardware or firmware. The auxiliary code might provide more context on the specific stage of initialization.

Causas comunes

  • Failure of a specific hardware component to respond during its self-test phase (e.g., an internal measurement ASIC, gate driver).
  • Issues with the internal clock synchronization or timing circuits on the control board.
  • Firmware corruption affecting a fundamental part of the hardware initialization routine.
  • An attempt to boot with an incompatible power unit or control board combination.
  • Persistent internal memory error preventing the drive from completing its boot sequence.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Execute a drive power cycle.

  2. 2

    Perform a full parameter reset to factory defaults (P96-01=1) to clear any potentially corrupt configuration that might interfere with initialization.

  3. 3

    Update the drive's main firmware to the latest compatible version.

  4. 4

    If option modules are present, power down the drive and remove them one by one to see if the fault clears, indicating an issue with a specific module.

  5. 5

    If the issue persists after these steps, the drive's main control board likely requires replacement.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas