A982

External warning 2

ABB · ACS580

¿Qué significa A982 ?

An external device configured as External Event 2 (parameters 31.03 and 31.04) has generated a warning. This indicates a potential issue with external equipment or sensors that should be investigated, though it may not cause an immediate drive trip. Addressing warnings proactively prevents escalation to faults.

Causas comunes

  • Elevated temperature on an external motor bearing, activating a thermal switch connected to the drive's configured digital input (P31.03, P31.04).
  • Low fluid level in an external process tank, causing a level switch to trigger a warning signal on the digital input.
  • Minor mechanical obstruction or drag in the connected machinery, increasing motor current marginally and triggering an external current monitoring relay set to a warning threshold.
  • Loose wire connection or corrosion on the external sensor's output terminal, leading to an intermittent warning signal on the input.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Determine the specific external sensor or device linked to the digital input configured by P31.03 (External Event 2 source).

  2. 2

    2. Use a multimeter to verify the voltage level at the drive's digital input terminal corresponding to the external warning.

  3. 3

    3. Inspect the external sensor and its associated process (e.g., temperature, pressure, level) for any out-of-range conditions that would trigger the warning.

  4. 4

    4. Confirm that P31.03 (External Event 2 source) and P31.04 (External Event 2 action) are set to the correct signal source and warning response.

  5. 5

    5. Clean and re-terminate the wiring connection from the external device to the drive's input terminal to eliminate potential intermittent contact issues.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026