2211
Current Measurement Failure
ABB · ACS800 Standard Firmware
¿Qué significa 2211 ?
A failure has occurred in a current transformer within the output current measurement circuit. This will lead to inaccurate or no current feedback for the drive, severely impacting motor control, protection functions, and overall drive performance.
Causas comunes
- Failure in the current measurement circuitry (e.g., current transformers, Hall effect sensors).
- Internal fault within the drive's current sensing hardware.
- Open circuit or short circuit in the current sensor signal path.
- Incorrect current sensor calibration or configuration (P1-01, P1-02).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check all current transformer connections to the Main Circuit Interface Board (INT) for secure contact and integrity.