LSU charge failed
ABB · ACS880
¿Qué significa 7584 ?
The supply unit (LSU) did not become ready (e.g., main contactor/breaker closing) within the expected timeframe. This indicates a problem with the LSU's pre-charging or readiness sequence. The drive cannot operate without a ready supply unit.
Causas comunes
- No incoming AC mains voltage present at the LSU's input terminals (e.g., L1, L2, L3) or one phase is missing.
- Main input contactor (or circuit breaker) for the LSU failed to close or its auxiliary contact did not provide feedback.
- Pre-charging circuit resistors or contactor within the LSU are faulty, preventing the DC link from charging correctly.
- DC link voltage did not reach the minimum threshold within the expected time, possibly due to excessive load or a short circuit.
- Control power supply (e.g., 24VDC) to the LSU's control board is missing or too low, preventing proper control sequence.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Verify the incoming AC mains voltage at the LSU's input terminals (e.g., L1, L2, L3) using a multimeter. Ensure all three phases are present and within tolerance.
- 2
Check the operational status of the external main contactor or circuit breaker supplying the LSU. Verify its auxiliary contacts are wired correctly to the LSU's control inputs.
- 3
With power off, measure the resistance of the pre-charging resistors within the LSU (if accessible) to check for open circuits.
- 4
Monitor the DC link voltage (e.g., via diagnostic menu) during the power-up sequence to see if it begins to charge and where it stalls.
- 5
Verify the control power supply (e.g., 24VDC) for the LSU's control board at its dedicated input terminals (e.g., X1) using a multimeter.