A794

BR data

ABB · ACS880

¿Qué significa A794 ?

One or more of the brake resistor data settings (parameters 43.0843.10) are incorrect or missing. This prevents the drive from correctly calculating brake resistor operation and protection. Incorrect data can lead to improper braking or resistor damage.

Causas comunes

  • Brake resistor nominal resistance (`P43.08` (Brake resistor resistance)) or power (`P43.09` (Brake resistor power)) values are either `0` or outside the valid range.
  • Brake chopper activation voltage (`P43.10` (Brake chopper ON voltage)) is set to an illogical or out-of-range value (e.g., below `DC bus undervoltage limit`).
  • Typographical error during manual parameter entry via the control panel or PC tool.
  • Corrupted parameter memory within the drive causing incorrect default or saved values for brake resistor data.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Retrieve the nameplate data from the physically installed brake resistor for its nominal resistance (Ohms) and rated power (Watts).

  2. 2

    Enter the correct nominal resistance value into drive parameter `P43.08` (Brake resistor resistance).

  3. 3

    Enter the correct rated power value into drive parameter `P43.09` (Brake resistor power).

  4. 4

    Verify the brake chopper activation voltage `P43.10` (Brake chopper ON voltage) is set to a reasonable value, typically `700VDC` for a `400V` class drive.

  5. 5

    If parameters were previously saved, try reloading a known-good parameter set from a PC tool (e.g., `DriveManager`).

Ver todos los códigos en este manual (116)
Datos técnicos verificados. Última actualización: March 2026