¿Qué significa 16153 ?
The PROFIsafe watchdog timer for the I/O module has expired, indicating a loss of cyclic communication or a prolonged period without expected safety messages from the F-Host. This can be due to network delays or a module responsiveness issue. This is a severity 3 error.
Causas comunes
- The PROFIsafe safety communication has not been refreshed within the expected time interval.
- Failure to receive periodic safety heartbeats from a connected device.
- Communication interruption affecting timely safety updates.
- Device offline or experiencing communication issues.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Restart the I/O module to re-establish communication.
- 2
If the error persists, increase the configured PROFIsafe watchdog time in the F-Host settings.