28700
F-device Mismatch of Safety Destination Address (V3 CPU)
ABB · PB610 Panel Builder 600 Programming Software
¿Qué significa 28700 ?
The safety destination address (F_Dest_Add) for F-device instance <n> in an AC500 V3 non-safety CPU PM56xx system does not match the expected value. This is a critical configuration error preventing safe PROFIsafe communication.
Causas comunes
- The F-device has received a safety message addressed to an incorrect destination.
- Configuration error in the safety addressing scheme.
- Incorrect routing of safety telegrams within the network.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check the Safety PLC configuration for F-device instance <n>.
- 2
Verify or change the switch address setting to match the configured F_Dest_Add.
- 3
Restart the Safety PLC.