311
Channel value difference too high
ABB · PB610 Panel Builder 600 Programming Software
¿Qué significa 311 ?
The difference between redundant channel values (e.g., from two sensors monitoring the same safety function) has exceeded the configured tolerance window. This indicates a significant discrepancy in sensor readings or a potential issue with one of the channels. This is a severity 3 error.
Causas comunes
- Difference between monitored channel values exceeds a defined limit.
- Discrepancy in sensor readings from redundant inputs.
- Calibration mismatch between channels.
- One channel experiencing a drift or failure.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Adjust the tolerance window setting for the affected channels in the safety configuration if the current value is overly restrictive.
- 2
Check the channel wiring for both affected channels for proper connections and signal integrity.
- 3
Verify the configuration and calibration of the sensors connected to the affected channels.
Datos técnicos verificados. Última actualización: March 2026