Testxx.Fault

Safety Test Output Data Inaccurate or Faulted

Allen-Bradley · Compact 5000 Digital I/O Modules

¿Qué significa Testxx.Fault ?

This boolean tag indicates that the data for a safety test output Testxx is inaccurate and cannot be trusted, or the channel is set to 'Not Used'. A tag value of '1' signifies bad data or a fault. If a short circuit is detected in Pulse Test or Power Supply mode, the output cannot be set to a safe state.

Causas comunes

  • An underlying hardware fault on the test output (e.g., short circuit, internal module fault, field power loss).
  • The test channel Testxx is intentionally set to 'Not Used' in the module configuration.
  • A short circuit detected on the test output while it is operating in Pulse Test or Power Supply mode.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Access Studio 5000 Logix Designer to view the module's diagnostic information and identify specific active fault conditions related to test channel Testxx (e.g., Testxx.ShortCircuit, Testxx.FieldPowerOff).

  2. 2

    Troubleshoot and resolve the specific underlying fault condition identified for test channel Testxx.

  3. 3

    Verify the module configuration in Studio 5000 Logix Designer to ensure Testxx is not intentionally set to 'Not Used'.

Ver todos los códigos en este manual (38)
Datos técnicos verificados. Última actualización: March 2026