Channel No Load (5069-OF4, 5069-OF4K, 5069-OF8)
Allen-Bradley · Compact 5000 I/O Analog Modules
¿Qué significa Chxx.NoLoad ?
This boolean tag indicates that the signal wire is disconnected from channel (xx) or the RTB is removed from the module. This condition is detected only when the channel is configured for current mode output. A value of 1 signifies a no-load condition.
Causas comunes
- Signal wire disconnected from channel (Chxx) terminals
- Removable Terminal Block (RTB) removed from the module
- No load or an open circuit detected on the channel (Chxx) output while in current mode.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Confirm that the signal wire is securely connected to the designated terminals of channel (Chxx).
- 2
Verify that the RTB is correctly installed on the module.
- 3
Check the load connected to the current output channel (Chxx) for continuity and proper connection.
Datos técnicos verificados. Última actualización: March 2026