ModuleStatus:FlashingRed

Recoverable Module Fault or Connection Timeout

Allen-Bradley · Compact 5000 I/O Analog Modules

¿Qué significa ModuleStatus:FlashingRed ?

The Module Status indicator is flashing red, which can signify several conditions: a module firmware update is in progress or failed, the device has experienced a recoverable fault, or a connection to the module has timed out. The specific cause needs to be determined via software diagnostics.

Causas comunes

  • Module firmware update is in progress
  • Module firmware update attempt failed
  • Device experienced a recoverable internal fault
  • Connection to the module has timed out (e.g., due to cable failure)

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Allow any module firmware update to progress to completion.

  2. 2

    If a firmware update failed, re-attempt the firmware update procedure.

  3. 3

    Use the Logix Designer application to access the module's configuration (Connection and Module Info categories) to determine the specific fault type.

  4. 4

    To clear a recoverable fault, cycle power to the module (power off, then on).

  5. 5

    To clear a recoverable fault, click 'Reset Module' in the Logix Designer application via the Module Info category of the Module Properties dialog box.

  6. 6

    Use the Logix Designer application to check the Connection category in Module Properties for connection timeout status and determine the cause (e.g., inspect Ethernet cable integrity).

Ver todos los códigos en este manual (33)
Datos técnicos verificados. Última actualización: March 2026