I x .Slave.CRC_LRCError

Modbus Slave CRC/LRC Error

Allen-Bradley · Compact 5000 I/O Serial Module

¿Qué significa I x .Slave.CRC_LRCError ?

This boolean tag indicates that a CRC (Cyclic Redundancy Check) or LRC (Longitudinal Redundancy Check) error occurred during Modbus slave communication. A value of 1 (Occurrence) means that the received Modbus message failed its integrity check, suggesting data corruption during transmission. This indicates an issue with the physical layer or data format.

Causas comunes

  • Noise or electromagnetic interference (EMI) on the Modbus communication line
  • Damaged or improperly shielded serial communication cable
  • Mismatch in CRC/LRC calculation method or setting between the Modbus master and slave
  • Incorrect communication line termination (e.g., missing or improper resistors)

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Inspect the serial communication cable for physical damage, proper shielding, and correct termination (e.g., 120 ohm resistors at ends of bus).

  2. 2

    Verify the Modbus master's CRC/LRC calculation method and settings match the slave module's expected method.

  3. 3

    Check for external sources of electromagnetic interference (EMI) affecting the communication line and implement mitigation measures.

  4. 4

    Measure the signal integrity on the Modbus communication lines using an oscilloscope to identify noise or signal degradation.