Traduciendo...
I xx .Command yy .BufferOverrun
Modbus Master Command Buffer Overrun
Allen-Bradley · Compact 5000 I/O Serial Module
¿Qué significa I xx .Command yy .BufferOverrun ?
This boolean tag indicates that a buffer overrun occurred during data reception for a specific Modbus master command (Command yy). A value of 1 (Occurrence) means the module's receive buffer overflowed because data arrived faster than it could be processed. This condition can lead to data loss and unreliable command responses.
Causas comunes
- Communication speed (baud rate) is too high for the module's processing capability for incoming data
- Modbus slave device sending excessive or unsolicited data
- Module resource limitations or temporary heavy load preventing timely buffer processing
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Reduce the baud rate setting in the module's configuration if the slave device is sending large amounts of data.
- 2
Ensure the module's firmware is up-to-date to optimize data processing and buffer handling.
- 3
Verify the Modbus slave device is not sending unsolicited or excessively large data packets for Command yy.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas
Fuente: Allen-Bradley Compact 5000 I/O Serial Module