24582

Program Already Owns Equipment Phase

Allen-Bradley · Logix 5000 Advanced Process Control and Drives

¿Qué significa 24582 ?

The PATT instruction tried to take ownership of the equipment phase, but the executing program already possesses ownership. This often occurs when the instruction is repeatedly executed.

Causas comunes

  • The PATT instruction is continuously executed without prior relinquishment of ownership, or without checking for existing ownership.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Ensure the PATT instruction is executed only once per state transition, or limit its execution to a single scan.

  2. 2

    Implement logic to check for existing ownership (e.g., using this result code 24582) before attempting to re-take ownership.

  3. 3

    Verify that a Detach from Equipment Phase (PDET) instruction is used to release ownership when program control is no longer required.