NumberOfSampInv (Status.2)

Statistical Invalid NumberOfSamples

Allen-Bradley · Logix 5000 Advanced Process Control and Drives

¿Qué significa NumberOfSampInv (Status.2) ?

The NumberOfSamples parameter configured for the statistical instruction is invalid or incompatible with the size of the StorageArray or WeightArray. This condition prevents the averaging algorithm from executing and holds the Out value.

Causas comunes

  • The NumberOfSamples input is outside the valid range of 1 to the minimum size of the StorageArray or WeightArray, or the array sizes are incorrectly defined.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the value of the NumberOfSamples input parameter — ensure it is an integer between 1 and the minimum defined size of either StorageArray or WeightArray.

  2. 2

    Check the declared sizes of StorageArray and WeightArray (if used) to ensure they are adequately dimensioned for the desired number of samples.