Overlap Error

Allen-Bradley · MicroLogix 1400 Programmable Controllers

¿Qué significa -2 ?

An output overlap is detected, meaning multiple functions are assigned to the same physical output. This is a configuration error (e.g., PTO0 and PTO1 attempting to use a single output) that causes the controller to fault, and the User Fault Routine does not execute.

Causas comunes

  • Two or more PTOX instructions configured to use the same physical output.
  • Conflicting output assignments for different controller functions (e.g., PTOX and a discrete output) inadvertently using the same terminal.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Review the PTOX instruction configuration for all PTOX instances (e.g., PTO0, PTO1) and verify that each is assigned to a unique physical output.

  2. 2

    Check for any other controller functions that might be inadvertently assigned to the same physical output as a PTOX instruction.

  3. 3

    Modify the program to ensure each physical output (e.g., Output 2, 3, or 4) is used by only one instruction at a time.