F39

Phase V to Gnd

Allen-Bradley · PowerFlex 4 Adjustable Frequency

¿Qué significa F39 ?

A grounded phase condition has been detected specifically on motor phase V or in the wiring connecting drive output terminal V to the motor. This indicates a direct short path to ground.

Causas comunes

  • Phase V winding shorted to ground in the motor.
  • Cable insulation failure between phase V and ground.
  • Internal drive fault with phase V output stage.
  • Grounding fault on phase V line conductor.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Disconnect the motor from the drive output terminals (U, V, W).

  2. 2

    Measure insulation resistance between drive output terminal V and earth ground using a megger at 500VDC; expect a reading greater than 1 MΩ.

  3. 3

    Measure insulation resistance between motor phase V and the motor frame using a megger at 500VDC; expect a reading greater than 1 MΩ.

  4. 4

    Inspect the wiring connecting drive output terminal V and motor phase V for any physical damage or signs of insulation breakdown.

Ver todos los códigos en este manual (24)