Phase VW Short
Allen-Bradley · PowerFlex 4 Adjustable Frequency
¿Qué significa F43 ?
A short circuit condition has been detected between motor phases V and W, or in the wiring connecting drive output terminals V and W to the motor. This indicates an unintended low-resistance path between these phases.
Causas comunes
- Short circuit between phase V and phase W windings in the motor.
- Internal short circuit in the drive's output power module.
- Power cable damage causing conductors V and W to short.
- Incorrect motor connection or wiring error.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Disconnect the motor from the drive output terminals (U, V, W).
- 2
Measure resistance between drive output terminals V and W with the motor disconnected; expect an open circuit (infinite resistance) if no internal drive fault.
- 3
Measure resistance between motor phases V and W; expect a low resistance reading (continuity across the motor winding).
- 4
Inspect the wiring between drive output terminals V, W and motor phases V, W for any physical damage or direct short circuits.