F002

Auxiliary Input

Allen-Bradley · PowerFlex 520-series Adjustable Frequency

¿Qué significa F002 ?

An external trip input (Auxiliary) has been activated, signaling an issue from an external device or safety circuit. This causes the drive to trip, protecting itself and connected machinery. This input is configurable via digital input parameters.

Causas comunes

  • External safety circuit (e.g., emergency stop button, safety gate switch) connected to a digital input (e.g., X12/DI3) has activated, opening the contact.
  • Faulty wiring or loose terminal connection on the auxiliary digital input circuit (e.g., X12), causing an unintended open circuit condition.
  • Malfunctioning external safety relay or sensor providing the auxiliary trip signal, leading to an erroneous fault condition.
  • Parameter P2-10 (Digital Input Function) incorrectly configured for a normally open (NO) contact when a normally closed (NC) contact is actually being used.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the status of external safety devices connected to the auxiliary input terminal (e.g., X12/DI3) by visually inspecting device status indicators or using a multimeter to check contact closure.

  2. 2

    Inspect all wiring continuity and terminal connections for the auxiliary input circuit from the external device to the drive's terminal block (e.g., X12) using a multimeter.

  3. 3

    Monitor the digital input status via the drive's display (e.g., P7-01 [DI Status]) to confirm the input's state changes accurately with the external safety device actuation.

  4. 4

    Check parameter P2-10 (Digital Input Function) to ensure it is configured correctly (e.g., 'Auxiliary Trip NC' or 'Auxiliary Trip NO') matching the contact type of the external device.

  5. 5

    If safe to do so, temporarily bypass the external auxiliary input at the drive terminal (e.g., X12/DI3) by shorting it to the common terminal to determine if the fault is external to the drive.

Ver todos los códigos en este manual (48)