Ground Fault

Allen-Bradley · PowerFlex 700

¿Qué significa 13 ?

A current path to earth ground greater than 25% of the drive rating has been detected on the output. This indicates an insulation breakdown or short circuit between the motor phases or wiring and ground, which is a severe safety and equipment risk.

Causas comunes

  • Short circuit between motor phases and ground.
  • Damaged motor winding insulation.
  • Faulty motor power cable.
  • Grounding issue within the drive or motor.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Check the motor for a grounded condition (e.g., measure insulation resistance from motor phases to ground).

  2. 2

    Check the external wiring between the drive output terminals and the motor for a grounded condition.