Overvoltage
Allen-Bradley · PowerFlex 700
¿Qué significa 5 ?
The DC bus voltage has exceeded its maximum permissible value. This can be caused by high incoming AC line voltage, transient voltage spikes, or regenerative energy from a decelerating motor, risking damage to the drive's DC bus capacitors.
Causas comunes
- DC bus voltage exceeds the overvoltage limit.
- Regenerative braking energy is not being dissipated effectively.
- Input line voltage is too high.
- Faulty braking chopper or resistor (if applicable).
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Monitor the incoming AC line voltage for high voltage conditions or transient spikes.
- 2
Extend the deceleration time (e.g., by increasing the deceleration ramp parameter).
- 3
Install a dynamic brake option (resistor and chopper circuit) to dissipate regenerative energy.