78
Flux Amps Reference Range
Allen-Bradley · PowerFlex 700
¿Qué significa 78 ?
The value for flux amps determined by the Autotune procedure exceeds the programmed [Motor NP FLA] parameter. This indicates a discrepancy between the motor's actual flux current characteristics and the configured nameplate full load amperage, possibly due to incorrect motor data entry or an improperly sized motor.
Causas comunes
- Calculated flux current reference is outside acceptable limits.
- Motor model parameters (e.g., P2-xx) are incorrect.
- Stator resistance estimation failure.
- Low motor terminal voltage during operation.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Reprogram [Motor NP FLA] parameter with the correct motor nameplate Full Load Amperage value.
- 2
Repeat the Autotune procedure.