Traduciendo...
11215

P2 Bus Dip

Allen-Bradley · PowerFlex 750

¿Qué significa 11215 ?

The DC bus voltage on port 2 has dipped more than 180V below the drive's bus memory when the drive is offline or in stand-alone mode. This indicates an unstable DC bus voltage, which can affect drive reliability.

Causas comunes

  • Transient voltage sag in the incoming AC line voltage (Port 2) from the utility grid or plant distribution system.
  • Intermittent connection or high resistance at the main input power terminals (R, S, T) for Port 2, causing voltage drops.
  • Degradation or failure of DC link capacitors (Port 2), leading to a loss of capacitance and inability to buffer voltage dips.
  • Abnormal regenerative energy feedback from an external braking resistor or motor (Port 2) causing bus voltage instability.
  • Faulty DC bus voltage sensor or its associated signal conditioning circuit (Port 2) providing an incorrect reading.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Use a power quality analyzer to monitor the 3-phase AC input voltage (Port 2) for sags or momentary interruptions.

  2. 2

    Inspect and tighten all input power wiring connections at the drive's L1, L2, L3 terminals (Port 2) and upstream devices.

  3. 3

    Inspect DC link capacitors (Port 2) for physical defects like bulging, leaking electrolyte, or discoloration.

  4. 4

    Verify the integrity and correct connection of any external braking resistors or regenerative units associated with Port 2.

  5. 5

    Measure the actual DC bus voltage across the P+ and N- terminals (Port 2) with a multimeter to verify the controller's displayed value.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Allen-Bradley PowerFlex 750