113

Tracking DataErr

Allen-Bradley · PowerFlex 750

¿Qué significa 113 ?

An internal data error affecting tracking data has occurred. This is a generic data integrity issue, potentially compromising the drive's ability to store or retrieve critical operational tracking information. Such errors can lead to unpredictable drive behavior or loss of diagnostic capabilities if left unresolved.

Causas comunes

  • Corruption of internal drive tracking data due to power fluctuations or electromagnetic interference (EMI).
  • Sudden power loss or brownout during a write operation to tracking data memory in non-volatile storage (NVS).
  • Internal non-volatile memory (NVS) hardware fault on the main control board (MCB).
  • Firmware bug related to tracking data management and storage routines.
  • Repeated write cycles to the same NVS sector leading to memory wear and data integrity issues.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Perform a full parameter reset to factory defaults (e.g., P0-01 to "Factory Reset") to clear potentially corrupted tracking data.

  2. 2

    2. Upload saved parameters from a reliable backup file to restore a known good configuration.

  3. 3

    3. Verify the stability of the incoming AC line voltage (e.g., 480V L1-L2-L3) and control power (e.g., 24VDC) for the drive.

  4. 4

    4. Check for and install any available firmware updates for the main control board (MCB) that may address data integrity issues.

  5. 5

    5. If the fault persists, the main control board (MCB) likely has a damaged non-volatile storage module and requires replacement.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026