Traduciendo...
124

App ID Changed

Allen-Bradley · PowerFlex 750

¿Qué significa 124 ?

The application firmware on the main control board has been updated or changed. While not necessarily an error, this fault indicates a firmware revision discrepancy that requires verification. Ensure that the new firmware is compatible with the existing configuration and application to avoid operational issues.

Causas comunes

  • Drive application firmware updated, resulting in a new application ID.
  • Firmware corruption leading to a fallback to a different, potentially older, application version.
  • Main control board replacement with a board containing different firmware revision.
  • Incorrect firmware file flashed onto the drive during a maintenance procedure.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Verify the current application firmware version displayed on the drive's HMI (e.g., 'P0-01') against the required version for the machine.

  2. 2

    2. Confirm that the installed firmware matches the application requirements and the project documentation.

  3. 3

    3. If a firmware update was intended, proceed with any necessary parameter migration or verification steps (e.g., using DriveTools SP).

  4. 4

    4. If the firmware change was unintentional, re-flash the correct application firmware using the manufacturer's specified tool.

  5. 5

    5. After firmware confirmation or update, perform a full drive parameter backup to a computer or memory card.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Allen-Bradley PowerFlex 750