Traduciendo...
29

Analog In Loss

Allen-Bradley · PowerFlex 750

¿Qué significa 29 ?

An analog input signal, which is vital for drive control, has been lost or is outside its expected range. This condition, if not addressed, can be configured (via P263 [Anlg In0 LssActn]) to stop the drive. It typically indicates a wiring issue, sensor failure, or a problem with the signal source, leading to a loss of critical control feedback.

Causas comunes

  • Loss of 4-20mA or 0-10VDC input signal due to a broken wire or disconnected terminal (e.g., 'AI0' or 'COM').
  • Analog input signal voltage/current falling below the programmed minimum threshold (e.g., P260 [Anlg In0 Min]).
  • External sensor or transducer failure providing the analog signal (e.g., pressure transducer outputting 0mA).
  • Improper scaling of the analog input parameter (e.g., P261 [Anlg In0 Max]) causing out-of-range detection.
  • Faulty analog input channel on the drive's control board.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Measure the voltage (0-10VDC) or current (4-20mA) at the drive's analog input terminals (e.g., 'AI0' and 'COM') to verify signal presence.

  2. 2

    2. Inspect the analog input wiring for breaks, loose connections, or corrosion at both the sensor/source and drive terminals.

  3. 3

    3. Verify the external sensor/transducer operation and its output signal using a calibrated multimeter at the sensor output terminals.

  4. 4

    4. Check P260 (Anlg In0 Min) and P261 (Anlg In0 Max) parameters to ensure the expected analog signal range is correctly defined.

  5. 5

    5. If the signal is confirmed good at the drive terminals but the fault persists, swap to an alternate analog input channel (if available) or replace the control board.

  6. 6

    6. Confirm P263 (Anlg In0 LssActn) is set appropriately for the desired drive response to analog input loss.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Allen-Bradley PowerFlex 750