FB TWOHAND Bit 1

Two-Hand Discrepancy Error - Input Pair 2

Beckhoff · TwinSAFE Logic FB

¿Qué significa FB TWOHAND Bit 1 ?

A discrepancy has been detected within the two channels of input pair 2 for the FB TWOHAND. This means the redundant hand actuation signals are not synchronizing correctly, indicating a potential issue with the two-hand device, its wiring, or incorrect timing. This will prevent safe two-hand operation and put the machine into a safe state.

Causas comunes

  • Wiring fault on one channel of input pair 2 (e.g., broken wire to input X5.1 or X5.2 on safety PLC).
  • Malfunctioning two-hand actuation button for input pair 2, causing differing actuation/release times between channels.
  • Electrical interference (EMI) on the signal lines of input pair 2, leading to false switching states.
  • Degraded contact within the safety pushbuttons for input pair 2, resulting in intermittent signal loss.
  • Discrepancy time parameter (e.g., P_TwoHandDiscTime) set too tight, causing false positives from normal button tolerance.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    1. Power down the safety system, then use a multimeter to measure the resistance of the wiring from each button of input pair 2 to its respective safety input terminal (e.g., X5.1, X5.2).

  2. 2

    2. With power restored, observe the diagnostic LEDs on the safety module for input pair 2 while actuating each button independently and simultaneously.

  3. 3

    3. Replace the push button switch assembly for input pair 2 if its internal contacts show resistance instability or failure during actuation tests.

  4. 4

    4. Inspect the shielded cabling for input pair 2; verify the shield is properly grounded at one end (e.g., control cabinet ground bar).

  5. 5

    5. Access the safety controller's programming interface and temporarily increase the 'TwoHandDiscTime' parameter (e.g., to 500ms) to rule out overly sensitive timing.

Ver todos los códigos en este manual (60)
Datos técnicos verificados. Última actualización: March 2026