Traduciendo...
F2816

Softstart fault power supply unit

Bosch Rexroth · IndraDrive MPx02

¿Qué significa F2816 ?

A fault has occurred in the softstart circuit of the power supply unit. The softstart limits inrush current during power-up to protect components. This fault indicates that the softstart mechanism either failed to activate, failed to limit current effectively, or timed out. This can lead to high current surges and potential damage upon power-on.

Causas comunes

  • Defective softstart resistors or relays
  • Control circuit failure for the softstart function
  • Excessive inrush current due to external factors (e.g., large capacitance)
  • Incorrect timing parameters for the softstart circuit
  • Temporary short circuit during power-up

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Measure the incoming AC supply voltage at the drive's input terminals (L1, L2, L3) and verify it matches the nominal voltage specified for the IndraDrive MPx02.

  2. 2

    Inspect all input power wiring, including main contactor connections and the drive's input terminals, for loose connections, signs of corrosion, or any physical damage.

  3. 3

    Check the IndraDrive MPx02 diagnostic display or HMI for any additional concurrent fault codes or specific status messages that appear during the power-up sequence.

  4. 4

    Verify drive parameters related to the power supply configuration, such as nominal input voltage (e.g., P-0-0200 in Rexroth), to ensure they correctly match the actual measured supply.

Ver todos los códigos en este manual (99)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Bosch Rexroth IndraDrive MPx02