F3122

Safety related holding system: system error

Bosch Rexroth · IndraDrive MPx02

¿Qué significa F3122 ?

This non-fatal safety error indicates a general system error within the safety-related holding system of the IndraDrive MPx02. This system is responsible for safely holding an axis at a standstill, typically involving the motor holding brake, and a system error implies compromised reliability of this safety function.

Causas comunes

  • Internal fault within the IndraDrive MPx02's safety module responsible for the holding system.
  • Faulty or incorrectly wired holding brake control circuit.
  • Issues with the brake monitoring feedback signals (if present).
  • Corrupted safety parameters related to the holding system.
  • Insufficient or unstable power supply to the safety-related components.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Perform a complete power cycle of the IndraDrive MPx02 to reset the safety module.

  2. 2

    Inspect all wiring related to the holding brake and its monitoring system for damage, loose connections, or incorrect termination.

  3. 3

    Verify the brake control signals (e.g., 24VDC to brake) and feedback signals for proper voltage levels and timing.

  4. 4

    Check relevant safety parameters in the IndraDrive MPx02 for consistency and valid configuration for the holding system.

  5. 5

    If possible, test the holding brake independently to confirm its mechanical and electrical integrity.