E3103
Dynamization failed
Bosch Rexroth · IndraDrive Troubleshooting
¿Qué significa E3103 ?
This warning occurs in normal operation when safety technology is activated. It indicates that no dynamization pulse occurred at the dynamization input within the time P-0-3223, Time interval for dynamization of safety function selection, or the pulse width deviates from P-0-3224, Duration of dynamization pulse of safety function selection. If a safety function is selected, this condition would trigger F3134 Dynamization time interval incorrect or F3135 Dynamization pulse width incorrect errors.
Causas comunes
- No dynamization pulse occurs at the dynamization input within the time P-0-3223.
- The pulse width at the dynamization input differs from the parameterized time P-0-3224.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Remove the cause of the error in the wiring of the dynamization input.