Softstart fault power supply unit
Bosch Rexroth · IndraDrive Troubleshooting
¿Qué significa F2816 ?
During the soft start process, which involves loading the DC bus capacitance, the DC bus voltage curve is monitored. Significant deviations from the expected curve suggest a defect in the power section of the HMV01 supply unit. This fault indicates a problem specifically during the initial power-up sequence.
Causas comunes
- Short circuit in DC bus.
- Load on DC bus (e.g., external braking resistor incorrectly connected).
- Insulation error in DC bus wiring or within the device/other connected devices.
- Final DC bus voltage not reached within a maximum time.
- Inadmissible voltage fluctuations or drop in supply mains during soft start.
- Device defective.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Check DC bus wiring for short circuits and remove any found.
- 2
Check DC bus wiring for load; verify correct connection of any external braking resistor.
- 3
Check DC bus wiring for insulation errors; if wiring is correct, systematically remove connected devices from the drive system step by step to identify the defective device.
- 4
Check for defects at loads externally connected to the DC bus.
- 5
Check mains voltage for inadmissibly dropped values during soft start.
- 6
Replace the device.