F8806
Timeout during loading process
Bosch Rexroth · IndraDrive Troubleshooting
¿Qué significa F8806 ?
During the initial loading of the DC bus (soft start) before switching on the power supply, the expected DC bus voltage could not be reached within the allotted time window. This indicates a problem with the DC bus charging circuit or excessive load.
Causas comunes
- Too many additional capacitance modules connected.
- Short circuit or low impedance load in the DC bus.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Reduce the number of additional capacitance modules.
- 2
Check wiring of the DC bus connection for short circuits or low impedance loads.
Datos técnicos verificados. Última actualización: March 2026
Fallas relacionadas