838

%s-axis for switchover in SERCOS phase 4 not ready -> Check ident number S-0-0021.

Bosch Rexroth · Motion Control

¿Qué significa 838 ?

The specified axis ('%s') is not ready for switchover to SERCOS phase 4 due to a missing or incorrect identification number. The fix suggests checking ident number S-0-0022, implying a discrepancy or an issue with the specific ident for phase 4. This is a servo loop or drive fault.

Causas comunes

  • Drive rejection of SERCOS phase 4 switching due to missing ident number S-0-0022.
  • Drive rejection of SERCOS phase 4 switching due to incorrect ident number S-0-0022.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Read out ident number S-0-0022 of the affected axis.

  2. 2

    Correct any missing or wrong value for ident number S-0-0022.

  3. 3

    Initiate a new SERCOS startup after correcting the ident number.