Traduciendo...
17

Control word timeout

Danfoss · VLT AutomationDrive FC 301/302

¿Qué significa 17 ?

No communication is detected from the control word source to the frequency converter. This warning is active only when parameter 8-04 Control Word Timeout Function is not set to [0] Off. If set to [5] Stop and trip, the drive will ramp down to a stop and issue an alarm.

Causas comunes

  • Communication interruption from the master controller (e.g., PLC, HMI) to the drive via fieldbus (e.g., Profibus, Ethernet/IP).
  • Incorrect fieldbus communication settings (e.g., baud rate, address, timeout period P8-04) between the drive and the master.
  • Faulty fieldbus cable (e.g., broken conductor, improper shielding) preventing data transmission.
  • Master controller stopped sending control words or entered an error state.
  • Drive's fieldbus option card malfunction or incorrect installation preventing proper communication.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify the fieldbus communication status on the master controller (PLC/HMI) and ensure it is sending data packets or control words.

  2. 2

    Inspect the fieldbus cable for proper connection, damage, and correct termination resistors at both ends of the segment.

  3. 3

    Check parameter 8-04 (Control Word Timeout Function) and 8-05 (Control Word Timeout Time) settings; adjust timeout time (e.g., increase from 1.5s to 3s) if network latency is high.

  4. 4

    Monitor the status of the fieldbus option card LEDs (e.g., green/red) for communication activity and errors.

  5. 5

    Perform a network diagnostic test (e.g., ping for Ethernet/IP, bus status for Profibus) from a connected device to verify connectivity.

Ver todos los códigos en este manual (66)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Danfoss VLT AutomationDrive FC 301/302