1795

DSP received too many unknown SPI telegrams / MCO power-up issue

Danfoss · VLT AutomationDrive FC 301/302

¿Qué significa 1795 ?

The digital signal processor (DSP) received an excessive number of unknown SPI (Serial Peripheral Interface) telegrams. This fault code can also indicate an MCO (Motor Control Option) power-up issue, potentially caused by poor EMC protection or improper grounding.

Causas comunes

  • Electromagnetic interference (EMI) ingress corrupting SPI (Serial Peripheral Interface) communication lines between internal modules.
  • Incompatible MCO (Motor Control Option) card firmware or hardware revision installed.
  • Faulty MCO card or a loose connection of its ribbon cable to the main control board.
  • Timing mismatch or clock synchronization issues on the SPI bus causing unknown telegram reception.
  • Internal component failure on either the DSP board or the MCO card causing spurious data transmission.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Verify secure seating of the MCO card in its designated slot and inspect ribbon cable connections.

  2. 2

    Check for and address potential sources of EMI near the drive and control cabinet wiring.

  3. 3

    Confirm the MCO card hardware revision is compatible with the main control board and drive firmware.

  4. 4

    Attempt to update the firmware of the MCO card, if applicable, using the specified programming tool.

  5. 5

    Temporarily remove the MCO card from its slot and power up the drive to see if the fault clears (indicates MCO issue).

Ver todos los códigos en este manual (66)