Traduciendo...
16

Short circuit

Danfoss · VLT HVAC Basic FC 101

¿Qué significa 16 ?

A direct short circuit condition has been detected either within the motor's windings or across its terminal connections. This is a highly critical fault that triggers a trip-lock, requiring a power cycle to reset after the cause is rectified. Operating with a short circuit can cause immediate and irreparable damage to the frequency converter's IGBTs or other power components.

Causas comunes

  • Direct phase-to-phase short circuit within the motor windings due to insulation failure.
  • Loose strands of conductor or foreign metallic objects causing a short circuit at the motor terminal block.
  • Severe damage to motor cable insulation, leading to direct conductor-to-conductor contact (phase-to-phase short).
  • Drive internal power component (IGBT) failure on the output stage, resulting in a permanent short.
  • Incorrect wiring in the motor terminal box, causing a misconnection (e.g., two phases directly connected).

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    Power off the drive and disconnect input power. Disconnect motor cables from drive output terminals (U, V, W).

  2. 2

    Measure resistance between each pair of motor phase terminals (U-V, V-W, W-U) at the motor. All three readings should be similar and low (e.g., < 1 Ohm for large motors).

  3. 3

    Visually inspect the motor terminal box for loose wires, metallic debris, or damaged insulation between phases.

  4. 4

    Perform an insulation resistance test (megger) phase-to-phase and phase-to-ground on the motor windings.

  5. 5

    If motor and cable tests are clear, a drive internal fault is likely. Contact authorized service personnel for internal diagnosis.

Ver todos los códigos en este manual (40)
Datos técnicos verificados. Última actualización: March 2026

Fallas relacionadas

Fuente: Danfoss VLT HVAC Basic FC 101