Motor overload temperature
Danfoss · VLT HVAC Drive FC 102
¿Qué significa 10 ?
According to the electronic thermal protection (ETR), the motor is too hot. This fault occurs when the motor runs with more than 100% overload for an extended period. Unresolved motor overheating risks severe motor damage or premature failure.
Causas comunes
- Motor operating continuously above 100% of its rated current, leading to excessive winding temperature.
- Incorrect motor data (P1-20 to P1-25) programmed in the frequency converter, causing inaccurate thermal model calculations.
- Insufficient motor cooling due to blocked ventilation fins, a faulty cooling fan, or high ambient operating temperature.
- Mechanical overload on the motor shaft due to process issues, worn bearings, or misaligned coupling.
Pasos de reparación & Lista de verificación
Haga clic en los pasos para seguir su progreso.
- 1
Measure the motor winding temperature directly using an infrared thermometer or an embedded RTD/thermistor if available.
- 2
Verify motor nameplate data (Voltage, Current, Frequency, RPM, Power Factor) is accurately entered into parameters P1-20 through P1-25.
- 3
Clear any obstructions from the motor's cooling fan and ventilation fins, and ensure adequate airflow in the motor's operating environment.
- 4
Measure the output current to the motor with a clamp meter during operation and compare it to the motor's rated current (P1-02).