Brake check

Danfoss · VLT Micro Drive FC 51

¿Qué significa 28 ?

The brake resistor is either not connected to the drive, or it is not functioning correctly (e.g., open circuit). This means the drive cannot dissipate regenerative energy, potentially leading to DC overvoltage faults during deceleration if braking is required.

Causas comunes

  • Open circuit in the external brake resistor wiring, such as a broken cable or loose connection at drive terminals B1/B2 or resistor terminals.
  • The external brake resistor itself has failed (e.g., internal element broken due to overheating or mechanical shock).
  • Incorrect brake resistor value (resistance or power rating) connected, causing the drive to misinterpret its presence.
  • Faulty internal current sensing circuit within the drive responsible for monitoring the brake resistor connection.

Pasos de reparación & Lista de verificación

Haga clic en los pasos para seguir su progreso.

  1. 1

    De-energize the drive and wait for DC bus discharge (verify 0VDC at DC+ / DC- terminals).

  2. 2

    Measure the resistance of the external brake resistor directly at its terminals, verifying it matches the specified value (e.g., 20 Ohms).

  3. 3

    Measure continuity of the brake resistor cables from the drive's B1 and B2 terminals to the resistor terminals.

  4. 4

    Confirm Parameter P5-10 (Brake Resistor Ohms) is set correctly to the actual resistance of the connected brake resistor.

  5. 5

    Inspect drive terminals B1 and B2 for secure connections and absence of corrosion.

Ver todos los códigos en este manual (51)
Datos técnicos verificados. Última actualización: March 2026